Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-0523-01181
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/27/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/27/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1.Previous comments not addressed. These plan review comments are not the latest comments entered per the electrical plan review on 6-8-2023. The response letter is dated 11-18-2020 ? Please submit the correct response and the correct revised plans. |
||
11/13/2023 | Commercial Structural | REQUIRES RESUBMIT | Your submittals indicates new rails, legs, roof/rail attachments (see sheet S-01 and SS-02). Ensure that these replacement equipment/panels still comply to the Uplift Calculation based on the 115 MPH wind gust and the Roof Load Calculation showing the maximum allowable of 40 lbs per point load ( NOTE: you show array 01 and 03 at 66 lbs per penetration) and maximum allowable of 4 lbs per square foot on roof. You may add a statement from your Arizona registered structural engineer on your drawing attesting to this requirement with his seal and signature. | ||
11/03/2023 | PDSD Application Completeness | REVIEW COMPLETED |