Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0523-01179
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/17/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
07/17/2023 Commercial Plumbing REQUIRES RESUBMIT 1. The minimum capacity for a hydromechanical grease interceptor is 25 GPM with a 50 pound grease capacity. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
2. The Josam Model 60100H series of grease interceptor requires the installation of an air control device prior to the inlet of the grease interceptor. Reference: Section 303.2, IPC 2018.
3. A 3-compartment sink requires an indirect drain. If the sink is only used to clean dishes, pots, and pans, the indirect drain can terminate with either an air break or an air gap. If food is handled in the 3-compartment sink, the indirect drain must terminate with and air gap and each of the sink compartments must have independent drains (i.e. no manifold). The sink cannot connect directly to a grease interceptor. Reference: Sections 802.1.2 and 802.1.7, IPC 2018.
[Initial comment: Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer and that the existing water closets are not draining through the grease interceptor. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. (Contact at Pima County Regional Wastewater Reclamation Department: Lucinda Hyatt, 520-724-6036, lucy.hyatt@pima.gov) Reference: Section 1003.1, IPC 2018.]
06/28/2023 PDSD Application Completeness REVIEW COMPLETED