Permit Number: TC-COM-0523-01179
Parcel: 13614001H

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0523-01179
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2023 Commercial Building APPROVED
06/12/2023 Commercial Electrical APPROVED
06/12/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
06/12/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Appliances (e.g. Unox oven.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device if required. Reference: Sections 608.1 and 608.3, IPC 2018
2. Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer and that the existing water closets are not draining through the grease interceptor. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. (Contact at Pima County Regional Wastewater Reclamation Department: Lucinda Hyatt, 520-724-6036, lucy.hyatt@pima.gov) Reference: Section 1003.1, IPC 2018.
05/08/2023 PDSD Application Completeness REVIEW COMPLETED