Permit Number: TC-COM-0523-01173
Parcel: 13704059A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0523-01173
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/17/2023 Commercial Plumbing REQUIRES RESUBMIT 1. Provide a backflow assembly to be directly after the new water meter. Reduced pressure backflow prevention assemblies are required at the water meter for buildings that have food service facilities.. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
2. Specify the material used for the water service pipe. Reference: Section 107.2.1, IBC 2018.
3. Provide the size of the replacement water service pipe. A 5/8” water meter is allowed to supply up to 20 GPM; verify that the increased pipe length will not result in inadequa1. Provide a backflow assembly to be directly after the new water meter. Reduced pressure backflow prevention assemblies are required at the water meter for buildings that have food service facilities.. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf
2. Specify the material used for the water service pipe. Reference: Section 107.2.1, IBC 2018.
3. Provide the size of the replacement water service pipe. A 5/8” water meter is allowed to supply up to 20 GPM; verify that the increased pipe length will not result in inadequate water pressure. Reference: Section 604.7, IPC 2018.
te water pressure. Reference: Section 604.7, IPC 2018.
05/03/2023 PDSD Application Completeness Express REVIEW COMPLETED