Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/30/2026 Addressing Validation REQUIRES RESUBMIT Please inlcude full unit number (171) and resubmit after other reviews are complete.
05/01/2026 Commercial Mechanical Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00642
ADDRESS/PARCEL: 943 E UNIVERSITY BL Unit:UNIT 171 TUCSON, AZ 85719
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation for the building to justify the capacity of the unit being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The unit itself will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.