Permit Number: TC-COM-0426-00633
Parcel: 133110150

Review Status: Requires Resubmit

Review Details: RESTAMP - COMMERCIAL v.1

Permit Number - TC-COM-0426-00633
Review Name: RESTAMP - COMMERCIAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2026 Site Engineering Express APPROVED
08/20/2026 Site Zoning Express APPROVED
08/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/21/2026 Water - PDSD Express REQUIRES RESUBMIT 1. Comments not addressed. [Initial comment: Provide the size of both the water service meter and the reduced pressure backflow preventer assembly serving this building. Reference: Section 107.2.1, IBC 2024.]
2. Comments not addressed. [Initial comment: Provide the total water demand served by the existing water meter. Reference: Section 107.2.1, IBC 2024.]
3. Plumbing sheets P0.1 and P1.1 have nt been included in the current submittal.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
08/21/2026 Fire New Construction Express REVIEW COMPLETED