Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0426-00633
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/26/2026 | Commercial Mechanical Standard | APPROVED | |||
| 05/26/2026 | Commercial Plumbing Standard | APPROVED | |||
| 05/27/2026 | Site Engineering Standard | APPROVED | |||
| 05/26/2026 | Site Zoning Standard | APPROVED | |||
| 05/21/2026 | Water - PDSD Standard | APPROVED | |||
| 05/18/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 06/04/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/26/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Sheet T1.0: Provide justification for the use of occupancy classification "B" for the 1,314 SF Fitness Center. The use of this area more closely resembles an occupancy classification of "A-3", gymnasium (without spectator seating) and subject to the provisions applicable to this occupancy. Update accordingly. Reference IBC 107.2.1 Sheet T1.0: Please provide a list of all deferred submittal items, separate permits, and special inspections applicable to this project. Reference IBC 107.2.1 Sheet T1.0: Please provide plan sheets SP1.0 and SP1.1 as listed in sheet index. Please ensure that Sheet SP1.1 includes an egress plan showing the length of common path of travel from the most remote point of the rooms, proposed exit paths, travel dimensions, exit access travel distances, and accessible egress. Reference IBC 107.2.1 Sheet T1.0: Please update sheet index to accurately reflect all sheets within the plan set. See also comment for Sheet A.1 Reflected Ceiling Plan. Reference IBC 107.2.1 Page 2 of 26: Survey-Provide plan sheet that is sealed, signed, and dated (current) per ARS 32-144, If page is for reference only, so notate on plan sheet. Typical all sheets with 2017 seal date. Page 2 of 26: Survey-Provide a unique page identifier for plan sheet and that is listed in the sheet index on page T1.0. Typical both survey sheets to be individually identified. Reference IBC 107.2.1 Sheet A1.1: Provide detail drawings or other substantiation that the new 4" concrete walk located at the exterior of Door 1 complies with, ANSI 302, 403, 404.2.3, IBC 1010.1.4 and 1010.1.6. Reference also ADA 202.2, 202.3 and 202.4. Typical also at new doors 2 and 3 Sheet A1.1: Update countertop note at Room 107 to show 34 inches AFF to coordinate with Detail 3 Sheet A4.1. Reference IBC 107.2.1 Sheet A1.1: Clearly demonstrate a maneuvering clearance at the pull side of Door 7 and the door located adjacent to Room 105 that complies with ANSI Section 404.2.3/ADA 404.2.4. Reference ADA 202.4 Sheet A1.1: Update elevation callouts, where provided, at all rooms to accurately reflect location of detail drawings. Reference IBC 107.2.1 Sheet A1.1: Update countertop note at Room 100 to show 30 inches AFF to coordinate with Detail 1 Sheet A4.1. Reference IBC 107.2.1 Sheet A2.1: Reflected Ceiling Plan-There are two plan sheets numbered A2.1. Please provide a unique page identifier and coordinate with Sheet Index on sheet T1.0 to accurately reflect all pages in the plan set. Reference IBC 107.2.1 Sheet A4.1: Detail 4-Provide a dining/work surface at the lounge table that complies with ANSI Section 902. Reference IBC 1110.14 Sheet A6.0: Provide substantiation that the door surface for the door types shown complies with the provisions of ANSI 404.2.9. Sheet A6.0: Door Schedule-Clearly demonstrate how Items C, D, and I, as listed in the Door Hardware Legend, comply with the provisions of IBC 1010.2 for each door with these items. Sheet S1: Provide a statement of special inspection complying with IBC 1704.3. In conjunction with this statement, please provide a fully executed Special Inspection Certificate for all inspections required in the statement. Reference IBC 1704.2.3 and 107.1 Sheet S2. Please detail required washer for sill plate anchor bolts. SDPWS 4.3.6.4.3 Sheet S2. Please list all engineering design criteria as outlined in IBC 1603.1 (exception). Sheet S2. Please list all applicable information for concrete as outlined in IBC 1901.5. Include minimum compressive strength of concrete. IBC 1904.1 Structural Calculations Page 1 of 16: Please provide ASCE Hazard Tool printout showing seismic design values. IBC 1604.2 Structural Calculations Page 1 of 16: Please provide calculations for: 1. 8.75x21 glulam beam. 2. Seismic design 3. Lateral / shearwall design 4. Epoxied rebar for footings. Structural Calculations Page 3 of 16: Basic wind speed for City of Tucson = 105 mph for risk category II structures, 110 mph for risk cat. III, per City Amendments. IBC 1609 Structural Calculations Page 15 of 16: Calculations showing footing pad dimensions that do not match plans at column B4. Please review. IBC 1604.2 |
||
| 05/26/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Sheet E2: Power plan on Sheet E4 shows the drinking fountain to be supplied by receptacle outlet on Circuit 23 in Panel RA. Provide appropriate circuit description of the circuit to show its clear and evident use. Reference NEC 408.4 Sheet E3: Clearly demonstrate occupant sensor controls at the new lighting in the Fitness Center complying with IECC 405.2.1.1. Reference IECC C503.6 Sheet E4: Provide GFCI protection for Circuit RA-23 where used for supply to the drinking fountain. Verify appropriate circuit identification and provide appropriate identification in panel schedule. See comment on Sheet E2. Reference NEC 422.5(A)(2). |
||
| 05/26/2026 | External Reviewers - Brown & Associates Standard | REQUIRES RESUBMIT | Electronic documents: construction documents are to be in one comprehensive, continuous plan set (not individual sheets or separated by discipline). Create a separate pdf file for each document type, i.e. Plan Set, Structural Calculations, Soils Report, etc. Provide a Narrative of Changes if revisions were made in addition to addressing previous comments. See Commercial Building and Commercial Electrical for associated specific comment responses. |
||
| 05/28/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | -Resolve all building comments. john.vincent@tucsonaz.gov 5203495581 |
||
| 06/04/2026 | Landfill Standard | REQUIRES RESUBMIT | Permittee must review Landfill Ordinance 10037. https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az/0-0-0-22345 The Landfill Ordinance Self-Certification Statement Form must be completed and submitted for approval. |
||
| 05/05/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |