Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0426-00633
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2026 | Landfill Standard | NOT REQUIRED | Subject building on property is outside of the 500-foot landfill boundary. | ||
| 08/04/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/04/2026 | Commercial Building Standard | REQUIRES RESUBMIT | 1. Sheet A1.1: Slope of surface within maneuvering clearances at door shall not be more than 1:48. Reference ANSI 404.2.3.1 2. Sheets S1 & S2: Engineer's stamp cut off. Please provide a clear stamp of the document. 3. Calculation Page 8 of 16: Minimum wind speed for City of Tucson is 105 mph for a Risk Category II structure. See City amendments. 4. Calculation Page 9 of 16: Wind speed listed as 115 mph on page 7, 90 mph on page 8, and 110 mph on page 9. Minimum wind speed for City for Tucson for Risk Cat II structure is 105 mph. Please submit calculations using a consistent design wind speed and pressure. If the calculation no longer applies, remove it from the packet. The listing of 110 mph on this page also appears to have been whited out, and it is presumed that the calculations below it are not accurate. Please review. 5. Calculation Page 10 of 16: wind pressure does not match that seen on other calculation pages. Please review. |
||
| 08/04/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Sheet E3: Exit signage shall not be placed at the door on the morth side of the fitness Center unl;ess the door swing is reversed in teh direction of egress travel. Reference IBC 1010.1.2.1. | ||
| 08/04/2026 | External Reviewers - Brown & Associates Standard | REQUIRES RESUBMIT | See posted comments | ||
| 07/10/2026 | Addressing Validation | REVIEW COMPLETED | The following has been satisfied as of 7/10/26: The address on the permit location 7401 E SPEEDWAY BL Unit: BLDG 3 does not match the address on the uploaded documents. It appears the work is at the clubhouse and not Bldg. 3. Please either update or remove the building number from the permit depending on how the clubhouse is addressed. Please either correct the address on the uploaded documents and resubmit or submit a change of address request in the permit sub-records. Please contact Pima County Addressing at addressing@pima.gov or 520-724-9512 to verify and add the unit if needed. |
||
| 07/17/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 06/29/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |