Permit Number: TC-COM-0426-00632
Parcel: 136254120

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0426-00632
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/29/2026 Commercial Plumbing Express REQUIRES RESUBMIT 1. The water service pipe shall not be less than ¾ inch (19 mm) in diameter. The internal diameter of ¾” PEX is 0.671 inches. Reference: Section 603.1, IPC 2024.
2. Based on Table E103.3.(2) and Table E103.3(3), IPC 2024, the calculated water demand is in the range of 14.6 GPM (if bathroom groups are used) to 16 GPM. With a maximum water velocity of 8 feet per second, at 14.6 GPM, the minimum size of PEX for the water service pipe is 1 inch; at 16 GPM, the minimum size of PEX is 1-1/4 inch.
3. Limiting the maximum water velocity to 8 feet per second, the PEX tubing has to be one nominal pipe size greater than the copper tubing size for a given demand.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
04/29/2026 PDSD Application Completeness Express REVIEW COMPLETED