Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0426-00622
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2026 Commercial Building APPROVED
07/08/2026 Site Zoning APPROVED
07/14/2026 Water - PDSD APPROVED
07/10/2026 Site Engineering NOT REQUIRED
07/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00622 (2101 N COUNTRY CLUB RD Unit:UNIT 101 TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide a complete set of electrical drawing for the scope of work being done.
Plans shall include (as necessary for scope of work), but may not be limited to items below:
2. Provide electrical load calculations, for the Main Panel showing it can support the additional electrical load, Per NEC 220.40.
3. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
4. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
5. Provide an electrical plan and Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
07/13/2026 Fire New Construction REVIEW COMPLETED
06/29/2026 PDSD Application Completeness Express REVIEW COMPLETED