Permit Number: TC-COM-0426-00615
Parcel: 122091500

Address:
4102 E LINDEN ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0426-00615
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2026 Commercial Building APPROVED
05/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/06/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00615 (4102 E LINDEN ST TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.
2. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
3. Provide conductor size and type for each new equipment, NEC chapter 3, wiring methods. Include wet location rating.
4. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
5. Show a GFCI and weather protected receptacle outlet on the same level within 25’ of exterior HVAC equipment, [NEC 210.62].
05/12/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00615
ADDRESS/PARCEL: 4102 E LINDEN ST TUCSON, AZ 85712

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. This permit is for the West Room only. Please clearly identify on the site plan which AC units are included under this permit. Currently, all three units are labeled as “AC 1” on the site plan, while the Notes section identifies them as AC 1.1, AC 1.2, and AC 1.3. Please revise the plans so the unit labels match throughout. Also, please remove the information regarding the unit replacement for the guest house since that work is being reviewed under permit TC-COM-0426-00608. Reference: Section 107.2.1, IBC 2024.
04/30/2026 PDSD Application Completeness Express REVIEW COMPLETED