Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0426-00611
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2026 Commercial Mechanical Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00611
ADDRESS/PARCEL: 5600 S MIDVALE PARK RD Unit:BLDG 4 UNIT 4303 TUCSON, AZ 85746

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Previous comment not addressed. Please show where the AC unit is located on the site plan. Reference: Section 107.2.1, IBC 2024. [Previous comment - Provide a site location for the location of the HVAC unit being replaced.]
2. Previous comment not addressed. Provide heating and cooling load calculations to justify the heating/cooling capacity of the AC unit. Reference: Section C403.1.1 and C502.2.3, IECC 2018. [Previous Comment - Replacement of AC units for residential occupancies will require a heating/cooling load calculation to justify the capacities of the units being installed…]
3. Provide the specifications for the replacement HVAC unit (e.g. manufacturer, model number, heating/cooling capacity, and efficiency ratings). The replacement units shall have an efficiency rating that is greater than or equal to the minimum required by the Department of Energy that went into effect on January 1, 2023.
05/13/2026 PDSD Application Completeness Express REVIEW COMPLETED