Permit Number: TC-COM-0426-00600
Parcel: 112060160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0426-00600
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2026 Commercial Building APPROVED
05/04/2026 Commercial Electrical APPROVED
05/11/2026 Site Zoning APPROVED
05/01/2026 Site Engineering NOT REQUIRED
05/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00600
ADDRESS/PARCEL: 2700 N CAMPBELL AV Unit:UNIT 100 TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. No valid Certificate of Occupancy was found for the previous Hair Salon. Permit # T12OT00119 for the previous Hair Salon is shown as void.
a. Provide mechanical plans. The plans shall identify all existing mechanical equipment, ceiling supply diffusers, return air grilles, exhaust fans (with the rated CFM), etc. (IBC 2024, Section 107.2.1)
b. Provide heating and cooling load calculations to verify the capacity of the existing unit, and include the equipment specifications on the drawing. (IECC 2018, Sections C403.3.1 and C403.2.2)
c. Provide an outdoor air ventilation schedule. Demonstrate that the mechanical system is designed to supply the minimum required outdoor airflow rate in accordance with code. (IMC 2024, Section 403.3.1.1)
05/07/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00600
ADDRESS/PARCEL: 2700 N CAMPBELL AV Unit:UNIT 100 TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Please show all new and existing waste piping, vent piping, and water piping serving the plumbing fixtures and equipment on a waste and vent diagram, and a water riser diagram. Reference: Section 107.2.1, 2024 IBC.
2. Coffee shops utilize milk and other dairy products, therefore, the 3-compartment sink, hand sink, and service sink are required to discharge through a grease interceptor. This requirement may be appealed to RWRD. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
a. Hand sinks in the kitchen area are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Please provide signage at both hand sink locations indicating that the sinks are to be used for handwashing only. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson.
b. If the 3-compartment sink is used only for washing, rinsing, and sanitizing utensils used for food service, the sink shall drain indirectly to the grease interceptor with an air gap or an air break. Reference: Sections 801.2, 802.1.1, and 802.1.7, IPC 2024.
3. Please provide a detail for the funnel drain and 3-compartment sink showing the indirect waste connection with the required air gap. Reference: Sections 802.1.7, IPC 2024.
4. The lavatory in the bathroom is being relocated. Please show there is a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 412.13, IPC 2024, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
5. Drop in Hand Sink (#9) is not specified in the equipment schedule on Sheet PE1. Please specify if this is new or existing?
6. Verify that the distance from the hot water source to the hot water termination for the lavatory complies with the requirements of Section C404.5, IECC 2018 (e.g., 24” for ½” hot water supply piping).
05/07/2026 Water - PDSD REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00600
ADDRESS/PARCEL: 2700 N CAMPBELL AV Unit:UNIT 100 TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2024.
05/12/2026 Fire New Construction REVIEW COMPLETED
04/27/2026 PDSD Application Completeness Express REVIEW COMPLETED