Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-0426-00596
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/23/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/23/2026 | Commercial Plumbing Express | REQUIRES RESUBMIT | 1. A 1 inch water meter, which, according to Tucson Water, is capable of supporting a maximum demand of 50 GPM, is currently serving this address. A 1 inch PEX water service pipe is limited to a maximum water velocity of 8 feet per second, or 14.5 GPM. What is the calculated water demand of this building? Reference: Section 107.2.1, IBC 2024. 2. Show the present location of the reduced pressure backflow assembly and the proposed new location of the assembly. Indicate the size of the assembly. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf . If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 04/22/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |