Permit Number: TC-COM-0426-00593
Parcel: 13101002H

Address:
5000 E 29TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0426-00593
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/13/2026 Commercial Plumbing APPROVED
07/13/2026 Water - PDSD APPROVED
07/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Previous comment not addressed and remains (Please revise the code summary and design criteria on all construction documents to reflect the codes and standards currently adopted by the City of Tucson, in accordance with Section 107.2.1 of the International Building Code. The applicable codes and standards shall include the following: • 2024 International Building Code (IBC) • 2017 ICC A117.1 Accessible and Usable Buildings and Facilities, as referenced by the IBC • 2024 International Plumbing Code (IPC) • 2023 National Electrical Code (NEC) • 2024 International Fire Code (IFC) • City of Tucson/Pima County Outdoor Lighting Code • All applicable local amendments to the above adopted codes Please revise the construction documents so the code analysis, general notes, life safety information, accessibility references, and design criteria are consistent throughout the entire drawing set. Refer to the City of Tucson adopted codes and amendments available through City of Tucson Planning and Development Services – Building Codes.

2. New coment for the 2nd review; Please provide the construction drawings and the structural calculations sealed by an Arizona licensed registrant on the next reviewfor the ramada structure. IBC 107.2.1


Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov
07/09/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00593 (5000 E 29TH ST TUCSON, AZ 85711)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

>>> The following comments were not fully addressed.

Electrical Review:

1. Provide a Grounding Electrode System at the detached structure per 250.31(A). Grounding electrode system and grounding electrode conductor. Required. >>> The way this section reads, both the shed and the ramada require separate grounding electrode systems. The ramada can claim the exception if it is fed by a single circuit, or a multiwire branch circuit.
2. Show each structure supplied by only one branch circuit of feeder, NEC 225.30. For the purpose of this section, a multiwire branch circuit shall be considered a single circuit. >>> Ramada is fed by two separate branch circuits.

Outdoor Lighting Review:
1. Show the ramada light fixture as full cutoff per OLC definition in chapter 2. See also OLC 401.2.1(3) & (4). >>> The provided light fixture does not appear to be full cutoff. Please verify that in the installed configuration that the fixture is indeed full cutoff.
07/09/2026 Outdoor Lighting REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00593 (5000 E 29TH ST TUCSON, AZ 85711)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

>>> The following comments were not fully addressed.

Electrical Review:

1. Provide a Grounding Electrode System at the detached structure per 250.31(A). Grounding electrode system and grounding electrode conductor. Required. >>> The way this section reads, both the shed and the ramada require separate grounding electrode systems. The ramada can claim the exception if it is fed by a single circuit, or a multiwire branch circuit.
2. Show each structure supplied by only one branch circuit of feeder, NEC 225.30. For the purpose of this section, a multiwire branch circuit shall be considered a single circuit. >>> Ramada is fed by two separate branch circuits.

Outdoor Lighting Review:
1. Show the ramada light fixture as full cutoff per OLC definition in chapter 2. See also OLC 401.2.1(3) & (4). >>> The provided light fixture does not appear to be full cutoff. Please verify that in the installed configuration that the fixture is indeed full cutoff.
07/10/2026 Site Engineering REQUIRES RESUBMIT Site Engineering Review

TC-COM-0426-00593
5000 E 29TH ST

Description: Ramada with lighting, Shade sail canopy, drinking fountain, food prep sink

Site Engineering comments are as follows:

1. This commercial building permit cannot be approved until the associated development package is approved by all reviewers. UDC Article 3.3.3.G.7.a

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
07/09/2026 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0426-00593 - TD-DEV-0626-00151
5000 E. 29th Street Tucson, AZ 85711
New Ramada with Lighting, Shade Sail Canopy, Fountain, Food Prep Sink (2nd Review)

TRANSMITTAL DATE: 7/9/2026

This site is located in the R-1 zone (UDC 4.7.8).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Follow up to previous comment 1: Site Zoning acknowledges a DP (TD-DEV-0626-00151) has been submitted. While the DP has not made it through the OK’s to submit yet, I have reviewed the submitted files to ensure consistency with the associated building permit. Although the plans submitted with the DP appear to match the associated building permit, Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
07/06/2026 Fire New Construction REVIEW COMPLETED
06/26/2026 PDSD Application Completeness Express REVIEW COMPLETED