Permit Number: TC-COM-0426-00593
Parcel: 13101002H

Address:
5000 E 29TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0426-00593
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/11/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please revise the code summary and design criteria on all construction documents to reflect the codes and standards currently adopted by the City of Tucson, in accordance with Section 107.2.1 of the International Building Code. The applicable codes and standards shall include the following:
• 2024 International Building Code (IBC)
• 2017 ICC A117.1 Accessible and Usable Buildings and Facilities, as referenced by the IBC
• 2024 International Plumbing Code (IPC)
• 2023 National Electrical Code (NEC)
• 2024 International Fire Code (IFC)
• City of Tucson/Pima County Outdoor Lighting Code
• All applicable local amendments to the above adopted codes
Please revise the construction documents so the code analysis, general notes, life safety information, accessibility references, and design criteria are consistent throughout the entire drawing set. Refer to the City of Tucson adopted codes and amendments available through City of Tucson Planning and Development Services – Building Codes.
2. Please provide the design and structural calculations for the shade sail canopy, including all attachment connections to the Ramada structure and the Tuff Shed Garden Ranch Shed. The calculations shall be prepared by a registered design professional and shall demonstrate compliance with applicable design loads and attachment requirements.
Please amend the construction drawings to include detailed information for the shade sail canopy, including connection details, attachment methods, supporting structural elements, and all required fasteners and hardware. IBC 107.2.7
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
05/07/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00593 (5000 E 29TH ST TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov


Electrical Review:

1. Provide a Grounding Electrode System at the detached structure per 250.31(A). Grounding electrode system and grounding electrode conductor. Required.
2. Show metal frame structure of the ramada, bonded with the equipment grounding conductor, 250.31(B).
3. Show each structure supplied by only one branch circuit of feeder, NEC 225.30. For the purpose of this section, a multiwire branch circuit shall be considered a single circuit.

Outdoor Lighting Review:
1. Show the ramada light fixture as full cutoff per OLC definition in chapter 2. See also OLC 401.2.1(3) & (4).
2. Show the ramada light fixture with a maximum color temperature of 3500K per OLC 402.1.
05/21/2026 Commercial Plumbing REQUIRES RESUBMIT 1. Freedom Park has both potable and non-potable water service. Clarify the location of the potable water service connection.
2. Will the irrigation service be non-potable?
3. Show the sizes of the potable and non-potable water pipes.
4. Show how the exposed water pipes are to be protected from freezing. Reference: Section 305.4, IPC 2024.
5. The food prep sink (detail 10/LS03) shall discharge to an indirect waste receptor with an air gap. Reference: Sections 801.2 and 802.1.1, IPC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
05/15/2026 Fire New Construction REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
05/15/2026 Site Engineering REQUIRES RESUBMIT Site Engineering Review

TC-COM-0426-00593
5000 E 29TH ST

Description: Ramada with lighting, Shade sail canopy, drinking fountain, food prep sink

Site Engineering comments are as follows:

1. A Development Package is required for the scope of this project. The content requirements may be found in Administrative Manual Section 2-06.
2. This commercial building permit cannot be approved until the associated development package is approved by all reviewers. UDC Article 3.3.3.G.7.a

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
05/15/2026 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0426-00593
5000 E. 29th Street Tucson, AZ 85711
New Ramada with Lighting, Shade Sail Canopy, Fountain, Food Prep Sink (1st Review)

TRANSMITTAL DATE: 5/15/2026

This site is located in the R-1 zone (UDC 4.7.8).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the minimum requirements is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/submittal_requirements.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
05/01/2026 PDSD Application Completeness Express REVIEW COMPLETED