Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL REVISION v.2
Permit Number - TC-COM-0426-00592
Review Name: COMMERCIAL REVIEW - FULL REVISION v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/27/2026 | Commercial Electrical Standard | APPROVED | |||
| 08/27/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 08/27/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | The number, location, and capacity of the “new” rooftop units shown on revision 3, sheet M-201 is different from those installed in 2009. A permit for the installation of any new rooftop units could not be found in our records. Provide the permit number that covered the landlord’s installation of new rooftop units. [Initial comment: Provide justification for installing HVAC units having a total cooling capacity of 604 MBH that exceeds the total cooling load of 328 MBH shown in the submitted calculations. Reference: Section C403.3.1, IECC 2024.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 08/27/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Provide the permit number that covered the landlord’s installation of new rooftop units and the revision to the existing natural gas piping. [Initial comment: The proposed rooftop units use gas-fired heating. Provide a design for the gas supply piping showing: 1. The location of the gas meter 2. The gas delivery pressure (e.g., 7” WG, 2 PSIG, or 5 PSIG) 3. The gas load for each piece of equipment in BTUH 4. The developed pipe length from the meter to each piece of equipment 5. The size and material of each pipe segment. 6. The location and downstream pressure of any pressure reducing valves] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 08/13/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |