Permit Number: TC-COM-0426-00592
Parcel: 105110710

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - TC-COM-0426-00592
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/15/2026 Commercial Mechanical Standard REQUIRES RESUBMIT The existing building does not have roof drains; it has scuppers that discharge to an area incapable of absorbing condensate flow without surface runoff. Terminate condensate drains at an approved disposal location. Reference: Section 307.2.1, IMC 2024, as amended by the City of Tucson. [Second comment: Comment not addressed.] [Initial comment: Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage (see Rooftop Unit Support detail, M-201). Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2024, as amended by the City of Tucson.]

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/12/2026 PDSD Application Completeness Express REVIEW COMPLETED