| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/15/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/15/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | The existing building does not have roof drains; it has scuppers that discharge to an area incapable of absorbing condensate flow without surface runoff. Terminate condensate drains at an approved disposal location. Reference: Section 307.2.1, IMC 2024, as amended by the City of Tucson. [Second comment: Comment not addressed.] [Initial comment: Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage (see Rooftop Unit Support detail, M-201). Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2024, as amended by the City of Tucson.] If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 06/12/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |