Permit Number: TC-COM-0426-00592
Parcel: 105110710

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0426-00592
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/08/2026 Commercial Plumbing Standard APPROVED
06/08/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/08/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Comment not addressed. [Initial comment: Condensate drains may not terminate in an area that is not capable of absorbing the condensate flow without surface drainage (see Rooftop Unit Support detail, M-201). Show the size, routing, and termination of the condensate drains. Reference: Section 307.2.1, IMC 2024, as amended by the City of Tucson.]
2. Comment not addressed. [Initial comment: Revise the ventilation calculations using the 2024 International Mechanical Code. The City of Tucson has adopted the 2024 IMC as the approved method for calculating ventilation requirements for occupancies other than ambulatory care facilities and I-2 occupancies. Reference: Section 401.2, IMC 2024.]
3. Comment not addressed. [Initial comment: The specified high temperature, undercounter dishwasher emits heat and steam into the room during operation Show that the heat and moisture loads from the proposed dishwasher are included in the HVAC load calculations for the space or install a Type II hood over the dishwashing machine. Reference: Exception (6), Section 507.1, IMC 2024.]
4. Comment not addressed. [Initial comment: Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g. Blodgett Oven 3C, Rapid Cook Oven 3D). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 6, IMC 2024.]
5. Comment not addressed. [Initial comment: Provide justification for installing an additional three tons of air conditioning into the café workroom for a total cooling capacity of approximately five tons. Reference: Section C403.3.1, IECC 2018.]
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
06/04/2026 PDSD Application Completeness Express REVIEW COMPLETED