Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0426-00590
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2026 | Fire New Construction | NOT REQUIRED | |||
| 05/11/2026 | Site Zoning | NOT REQUIRED | |||
| 05/12/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/05/2026 | Commercial Building | REQUIRES RESUBMIT | The location and required working space of electrical panel boards and over current protection devices shall not be designated for storage. Such devices shall not be located in clothes closets, bathrooms, or over the steps of a stairway. E3405.4 Please propose a new location. | ||
| 05/04/2026 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0426-00590 (2602 N BALBOA AV Unit:BLDG 0 UNIT 2 TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Provide a floorplan, showing the location of the electrical panel. The fire appears to have been in a cloths closet, and the damaged panel cannot remain in this location. NEC 240.24(D): Overcurrent protective devices shall not be located in the vicinity of easily ignitable material, such as in clothes closets. 2. Show panel location with sufficient working clearance as required by NEC 110.26. (Three feet deep, 6.5 feet high and minimum 30 inches wide.). |
||
| 04/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |