Permit Number: TC-COM-0426-00586
Parcel: 127122650

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-0426-00586
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2026 Commercial Building Standard APPROVED
07/16/2026 Commercial Mechanical Standard APPROVED
07/16/2026 Commercial Plumbing Standard APPROVED
07/16/2026 Water - PDSD Standard APPROVED
07/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/16/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00586 (5721 E BROADWAY BL TUCSON, AZ 85711)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

>>> Comments were not fully addressed. A COMcheck requires a dated signature by the individual who prepared the report in order to be valid.
1. Provide complete compliance with the 2018 IECC for the interior lighting, including sensors and lighting controls as required. (typically COMcheck.).
07/17/2026 Fire New Construction Standard REQUIRES RESUBMIT -See previous fire comments. You did not address the comments. Provide a response and resolve comments.
john.vincent@tucsonaz.gov
5203495581
07/16/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0426-00586 (5721 E BROADWAY BL TUCSON, AZ 85711)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf


>>> These comments were not fully addressed. (additional notes marked with ‘>>>’ below.).

1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code. Lighting fixtures ‘M’ and ‘N’.
2. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
3. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. >>> Lighting Fixture ‘N’ appears to be an LED strip light type fixture. This is considered unshielded. See also the definition, in chapter 2, of a light-fixture. >>> See also OLC 401.2.1(4). An architectural feature or overhang does not give this unshielded lighting fixture exemption from the unshielded lumen requirements.
6. Show lamps with a maximum of 3500K color temperature, OLC 402.1. >>> Lighting Fixture ‘M’ is shown with a 4000K color temperature. Lighting Fixture ‘N’ must show a color temperature as well. >>> This color temperature requirement cannot be ignored and dismissed. Submit lighting fixtures that meet this requirement to show compliance with the adopted Outdoor Lighting Code. An appeal to the Building Official is required for an exception for a color changing fixture that includes a 6500K color temperature setting.
7. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
8. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

9. Specify any exceptions used.

10. Provide Curfew lighting controls If applicable Per section 403. >>> Curfew controls are required for unshielded lighting fixtures such as ‘N’.
06/29/2026 PDSD Application Completeness Express REVIEW COMPLETED