Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0426-00585
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2026 | Outdoor Lighting Standard | NOT REQUIRED | Outdoor lighting reviewed and approved per TC-COM-0725-01290 . | ||
| 05/01/2026 | Site Engineering Standard | NOT REQUIRED | |||
| 05/19/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/07/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions regarding this review, please contact CDRC@tucsonaz.gov. Unable to process. The address on the uploaded site plan and permit application is incomplete. It appears that there are multiple addresses associated with the address 3105 N CAMPBELL AV. Please submit a change of address request through the permit sub records tab to add Unit numbers to the permit location and ensure it matches the unit listed in the construction plans. If there are three separate meters being used with their own units then please include all three units on addressing. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For help navigating sub records: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf |
||
| 05/08/2026 | Commercial Building Standard | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov 1. Please amend the list of the adopted applicable codes, and the code references throughout the plan set, as the following codes are now being enforced from the adopting ordinance. IBC 107.2.1 2024 International Building Code (IBC) 2017 ICC A117.1 Accessibility Code (by reference) 2024 International Mechanical Code (IMC) 2024 International Plumbing Code (IPC) 2023 National Electrical Code (NEC) 2024 International Fire Code (IFC) 2024 International Fuel Gas (IFGC) 2018 International Energy Conservation Code (IECC) Local Amendments to Above Codes ( www.tucsonaz.gov/pdsd/building-codes ) 2. Please reference the shell permit number the construction drawings. IBC 107.2.1 & our Commercial Plan Submittal Requirements https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf 3. Please amend the plan set or the Sheet Index, so all the drawing sheets in this permit’s scope are listed in the index and the index includes all the sheets in the plan set. IBC 107.2.1 For example, sheets M005,M101, M102, E110 are included in the plan set but not listed in the Sheet Index and Sheets M019, M020, M021, P102 are listed in the Sheet Index but not included in the plan set. 4.Please update the drawings to be incompliance with the 2017 ICC A117.1 edition of Accessible and Usable Buildings and Facilities For example the size of the turning space has increased to a 67” circle per 2017 ICC A117.1 304.3.1 and the size of the clear floor space has increased to 52” by 30”. 2017 ICC A117.1 305.3.1 Please contact me if you have any questions about the above comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 05/07/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0426-00585 (3105 N CAMPBELL AV TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Show the location of the SES and meter locations for the building. The shell permit, TC-COM-0725-01290, shows the SES located at the NW corner. There is a recessed existing wall that contains all the SES and meters. Your drawing shows WH-1 and multiple sinks and counter space where there should be an existing wall and SES/meter equipment. See clouded area on sheet E100. 2. Show the one-line diagram back to the specific 200A disconnect and meters that are being used. Each meter should have it’s own unit number, which must be included on the plans and on the permit for TEP electrical clearance. 3. Panels ‘A’, ‘B’ & ‘C’ appear to be new. They are not shown on the shell permit electrical, TC-COM-0725-01290. 4. Provide Fault Current Analysis and show new equipment/panels AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2023 NEC 110.24. 5. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2023 NEC 110.10. |
||
| 05/14/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Clarify the identification tags for the rooftop units. The three units shown on the roof plan, the mechanical floor plan, the plumbing roof plan, and on the equipment schedule are identified as RTU-1, RTU-2, RTU-3, and RTU-4. 2. Provide heating and cooling load calculations to justify the additional heating/cooling capacity of RTU-3. Reference: Section C403.1.1 and C403.3.1, IECC 2018. 3. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2024. 4. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Footnote g, Table 403.3.1.1, IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 05/14/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | 1. The International Plumbing Code 2024, the International Fuel Gas Code 2024, and the International Energy Conservation Code 2018, are the controlling codes for this activity. Correct the code citations in the specifications. 2. Provide a metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 604.4, IPC 2024 and Section 606.4, ICC/ANSI A117.1-09. 3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5.1, IECC 2018. 4. A hand wash sink located in the kitchen area shall either discharge through a grease interceptor or have a sign posted above it stating: “HANDWASH SINK ONLY! NO FOOD PREPARATIONOR DISHWASHING ALLOWED”. Reference: Section 1003.3(A), IPC 2024 as amended by the City of Tucson. 5. Floor sinks, floor drains, and trench drains in the kitchen shall discharge through a grease interceptor. Reference: Section 1003.3, IPC 2024, as amended by the City of Tucson. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 05/19/2026 | Fire New Construction Standard | REQUIRES RESUBMIT | Resolve all building comments. john.vincent@tucsonaz.gov 5203495581 |
||
| 05/18/2026 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons Zoning Section Review PROJECT: TC-COM-0426-00585 - TD-DEV-0425-00116 3105 N. Campbell Ave. Tucson, AZ 85719 Commercial TI to Bakery (1st Review) TRANSMITTAL DATE: 5/18/2026 This site is located in the C-1 zone (UDC 4.7.20). Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. 1. Comment: New outdoor seating is proposed next to the front doors however this was not called out in the associated Development Package (TD-DEV-0425-00116). If outdoor seating is proposed as shown on the plans, please revise TD-DEV-0425-00116 to account for this new seating area. 2. Comment: Per communication with Nicholas Ross (Site Zoning Section Manager), TD-DEV-0425-00116 calls out Food Service use as being 630sf at this site. Please clearly draw, label, and provide calculations for this seating area to ensure compliance with the associated Development Package. 3. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 05/14/2026 | Water - PDSD Standard | REQUIRES RESUBMIT | Provide the size of the water meter serving this suite, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2024. | ||
| 04/24/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |