Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/21/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions about this review, please contact us at CDRC@tucsonaz.gov
Incomplete submittal; Site plan missing complete project address. Please update site plan and resubmit.
How to request a change of address:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
Step-by-Step instructions on how to resubmit plans: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
04/21/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00580 (1050 W PRINCE RD Unit:BLDG 1 TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide an electrical riser diagram, NEC 230.9. Notate the grounding and bonding method, NEC 250.20(B), 250.24, 250.30(A)(4). Metallic gas lines must be bonded and not be used as the primary grounding method, NEC 250.50, 250.52(B)(1).
a. Show each meter and address/unit associated with each meter.
b. Show bus bar rating and AIC ratings.
2. This site is only qualified for one electrical meter/service. The provided site plans shows two. Please clarify.
04/21/2026 PDSD Application Completeness Express REVIEW COMPLETED