Permit Number: TC-COM-0426-00563
Parcel: 107143750

Address:
2455 N 1ST AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0426-00563
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2026 Commercial Electrical Standard APPROVED
05/11/2026 Commercial Mechanical Standard APPROVED
05/11/2026 Water - PDSD Standard APPROVED
04/24/2026 Site Engineering Standard NOT REQUIRED
05/13/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/11/2026 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00563
ADDRESS/PARCEL: (2455 N 1ST AV TUCSON, AZ 85719)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. VACANT AREA
a. Please block out the areas staying vacant and label them as such.
2. CASHIER (Please comply to the following.) Provide drawings illustrating this condition.
a. The tops work surfaces shall be 28 inches min & 34 inches max above the floor per ICC A117.1 sec 902.4.
b. Sec 306.3.3 Knee clearance shall be 11 inches min in depth at 9 inches above the floor, and 8 inches min in depth at 27 inches above the floor.
c. Sec 306.2.4 Additional toe clearance space extending greater than 6 inches beyond the available knee clearance at 9 inches above the floor.
d. Sec 306.3 Knee clearance shall be 30 inches min in width.
e. 904.3.2 Parallel approach, the counter surface 36 inches min length.
f. 904.3.3 Forward approach, the counter surface 30 inches min length.COM-0426-00601 (1741 N 6TH AV TUCSON, AZ 85705)
3. RESTROOM SIGN: Provide the following.
a. Directional signage indicating the location to the required public toilet facilities shall be posted in a lobby, corridor, aisle or similar space, such that the sign can be readily seen from the main entrance to the building or tenant space. IBC 2902.4.1
4. SIGN
a. Please submit a separate sign permit for any signs associated with this project.
5. Locate/label on the drawing the drinking fountain and the mop sink.
6. EGRESS
a. Egress through intervening spaces. IBC 1016.2
b. Exception 2: Means of egress are not prohibited through stockrooms in Group M occupancies where all of the following are met.
i. The stock is of the same hazard classification as that found in the main retail area.
c. Not more than 50 percent of the exit access is through the stockroom.
d. The stockroom is not subject to locking from the egress side.
e. There is a demarcated, minimum 44-inch-wide aisle defined by full- or partial-height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions.
f. Please clearly show the storage racks/shelves & the demarcated aisle with dimension & marking on the floor such as paint stripes, etc
7. Please resubmit.
05/11/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00563
ADDRESS/PARCEL: 2455 N 1ST AV TUCSON, AZ 85719
Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. A service sink and drinking fountain are required based on the minimum plumbing fixture calculations, but the fixture count table on Sheet A2.2 currently lists zero provided for both fixtures. Please revise the plans to show the required drinking fountain and service sink on the floor plans, including any associated revisions to the plumbing system. Reference: Sections 107.2.1 and 2902.1, IBC 2024.
05/04/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor lighting review cannot be approved until TC-COM-0326-00377 is approved. Resubmit when this existing permit is resolved and approved.
05/12/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Olga Salazar
Planning & Development Services Department – Zoning Review Section

PROJECT:
TC-COM-0426-00563 – Commercial Building
8800 E Tanque Verde Road, AZ 85749
Plan Review (1st Review)

TRANSMITTAL DATE: May 12, 2026

This site is zoned C-3 (UDC Section 4.7.22). “Smoke shop” is a permitted land use in the C-2 zone.

1. COMMENT: Per the Smoke Shop Certification letter dated November 20, 2025, the existing smoke shop is nonconforming with City of Tucson Unified Development Code (UDC) sections 4.9.9.H.1 and 4.9.9.H.3. On cover sheet, add a note to include this information.

2. COMMENT: Zoning cannot locate an approved Development Package that includes the sidewalk improvements made around 2023 along the sidewalk on North 1st Avenue. Demonstrate that the sidewalk complies with Technical Standards Manual Section 7-01.0.0: Pedestrian Access.

3. COMMENT: Clarify if the five (5) parking spaces are new proposed spaces. If so, this addition will require submittal of a Development Package.

4. COMMENT: Remove the bicycle parking calculations from the cover sheet, as no site improvements are proposed.

5. COMMENT: More comments may be forthcoming based on the next submittal's response.

If you have any questions about this transmittal, please contact Olga Salazar at Olga.Salazar@tucsonaz.gov.
05/13/2026 Fire New Construction Standard REVIEW COMPLETED
04/21/2026 PDSD Application Completeness Express REVIEW COMPLETED