Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0426-00523
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2026 Site Zoning APPROVED Approved w/ Main Plan Set: TC-COM-0426-00503
04/28/2026 Fire New Construction NOT REQUIRED
04/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/30/2026 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
TC-COM-0426-00503 Master Permit
1. Plan Review Comment – Structural / Architectural Clarifications
Additional Architectural Details Required:
Please provide supplemental architectural drawings and details to clearly depict the construction and code compliance of the proposed work. IBC 107.2.1
A. Detail 1/S1.2:
This detail references an existing guardrail (“(E) Guardrail – Ref Arch’l”). Please provide the corresponding architectural reference detail or sheet where the guardrail design and compliance are shown.
B. Detail 2/S1.2 – New Framed Wall:
Please provide a complete wall assembly detail, including but not limited to: overall height, framing, exterior finish, water-resistive barrier, weep screed location, flashing details, and stucco system. Ensure compliance with IBC 107.2.4 and applicable provisions of IBC Chapter 14 (Exterior Walls).
C. Detail 8/S1.2:
Provide a complete wall assembly detail consistent with the requirements noted above for Detail 2/S1.2.
D. Deck Framing Ventilation:
Please clarify whether the underside of the deck framing is enclosed. If enclosed, provide details demonstrating compliance with required ventilation provisions in accordance with IBC 2304.2.5.
2. Structural Drawings
A. Please expand the Balcony replacement schedule to include the other 6 items detailed on sheet S1.2. IBC 107.2.1 For example, show where details 2,4, 5, 6, 7, and 8 occur.
3. Structural Calculations:
A. Please submit structural calculations for the proposed design, sealed and signed by an Arizona-licensed design professional. IBC 107.2.7
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/15/2026 PDSD Application Completeness Express REVIEW COMPLETED