Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0426-00495
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2026 | Commercial Building | APPROVED | |||
| 04/17/2026 | Site Engineering | APPROVED | |||
| 04/21/2026 | Site Zoning | NOT REQUIRED | Per communication w/ Nick Ross and Loran Shamis, public schools are exempt from Site Zoning review. | ||
| 04/27/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/20/2026 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-0426-00495 (3725 N FLOWING WELLS RD TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC). Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Show PV interconnection in compliance with NEC 705.32. Reference also NEC 230.95. 705.32 Ground-Fault Protection. Provide a GFCI PV backfeed breaker at the main panel/switchboard. |
||
| 04/24/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 04/13/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |