Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-0426-00490
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2026 | Site Engineering Standard | APPROVED | |||
| 06/12/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/29/2026 | Commercial Building Standard | REQUIRES RESUBMIT | May 29, 2026 2nd Review Benson Hwy 880 LLC Attn: Andrew Kevelson 4847 N. Louis River Way Tucson, Arizona 85718 Re: 880 BENSON DISPENSARY NEW BUILDING City of Tucson Permit Number: TC-COM-0426-00490 Stantec Project Number: 185215066 Stantec File Number: TUC-26-025 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms M V-B 3,426 55 No Yes Separate Permits: Fire alarm and signage. Deferred Submittals: Pre-engineered wood trusses. Special Inspections: Epoxy and expansion anchors, structural steel, field welding, masonry. GENERAL COMMENTS 1. Addressed. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. 3. Addressed. Sheet G002 1. Addressed. Sheet A020 1. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS Sheet E0.5 1. Previous Comment: Please provide an engineered light pole foundation plan and structural calculations to accompany the design. [Ref. IBC 2024 Sec. 1604] Still Required: This comment was not addressed in the lates submittal. Please provide the requested engineered light pole foundation design and accompanying structural calculaitons. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 05/29/2026 | Commercial Electrical Standard | REQUIRES RESUBMIT | May 29, 2026 2nd Review Benson Hwy 880 LLC Attn: Andrew Kevelson 4847 N. Louis River Way Tucson, Arizona 85718 Re: 880 BENSON DISPENSARY NEW BUILDING City of Tucson Permit Number: TC-COM-0426-00490 Stantec Project Number: 185215066 Stantec File Number: TUC-26-025 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms M V-B 3,426 55 No Yes Separate Permits: Fire alarm and signage. Deferred Submittals: Pre-engineered wood trusses. Special Inspections: Epoxy and expansion anchors, structural steel, field welding, masonry. GENERAL COMMENTS 1. Addressed. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. 3. Addressed. Sheet G002 1. Addressed. Sheet A020 1. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS Sheet E0.5 1. Previous Comment: Please provide an engineered light pole foundation plan and structural calculations to accompany the design. [Ref. IBC 2024 Sec. 1604] Still Required: This comment was not addressed in the lates submittal. Please provide the requested engineered light pole foundation design and accompanying structural calculaitons. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 05/29/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | May 29, 2026 2nd Review Benson Hwy 880 LLC Attn: Andrew Kevelson 4847 N. Louis River Way Tucson, Arizona 85718 Re: 880 BENSON DISPENSARY NEW BUILDING City of Tucson Permit Number: TC-COM-0426-00490 Stantec Project Number: 185215066 Stantec File Number: TUC-26-025 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms M V-B 3,426 55 No Yes Separate Permits: Fire alarm and signage. Deferred Submittals: Pre-engineered wood trusses. Special Inspections: Epoxy and expansion anchors, structural steel, field welding, masonry. GENERAL COMMENTS 1. Addressed. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. 3. Addressed. Sheet G002 1. Addressed. Sheet A020 1. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS Sheet E0.5 1. Previous Comment: Please provide an engineered light pole foundation plan and structural calculations to accompany the design. [Ref. IBC 2024 Sec. 1604] Still Required: This comment was not addressed in the lates submittal. Please provide the requested engineered light pole foundation design and accompanying structural calculaitons. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 05/29/2026 | Commercial Plumbing Standard | REQUIRES RESUBMIT | May 29, 2026 2nd Review Benson Hwy 880 LLC Attn: Andrew Kevelson 4847 N. Louis River Way Tucson, Arizona 85718 Re: 880 BENSON DISPENSARY NEW BUILDING City of Tucson Permit Number: TC-COM-0426-00490 Stantec Project Number: 185215066 Stantec File Number: TUC-26-025 Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken. The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. Occupancy Group Construction Type Area (Square feet) Occupant Load Automatic Fire Sprinklers Fire Alarms M V-B 3,426 55 No Yes Separate Permits: Fire alarm and signage. Deferred Submittals: Pre-engineered wood trusses. Special Inspections: Epoxy and expansion anchors, structural steel, field welding, masonry. GENERAL COMMENTS 1. Addressed. ARCHITECTURAL COMMENTS General 1. Addressed. 2. Addressed. 3. Addressed. Sheet G002 1. Addressed. Sheet A020 1. Addressed. STRUCTURAL COMMENTS Sheet S1.0 1. Addressed. MECHANICAL COMMENTS There are no comments. PLUMBING COMMENTS Sheet P1.0 1. Addressed. ELECTRICAL COMMENTS Sheet E0.5 1. Previous Comment: Please provide an engineered light pole foundation plan and structural calculations to accompany the design. [Ref. IBC 2024 Sec. 1604] Still Required: This comment was not addressed in the lates submittal. Please provide the requested engineered light pole foundation design and accompanying structural calculaitons. Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline. Plans reviewed by: Trevor Bies, Senior Plan Reviewer 602-338-9922 trevor.bies@stantec.com |
||
| 06/12/2026 | Site Zoning Standard | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Jeffrey W. Cassidy, Planner Planning & Development Services Department – Current Zoning Review Section PROJECT: TC-COM-0426-00490 – Commercial – A NEW 3,426 SF GROUND-UP DISPENSARY REPLACING THE EXISTING GAS STATION AND CONVENIENCE STORE 880 E BENSON HY TUCSON, AZ 85713 (C-2 Zoning) Commercial Building Plan Review – 2nd Review TRANSMITTAL DATE: June 12, 2026 This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM). 1. COMMENT: Provide the incomplete development package and rezoning case numbers, TD-DEV-0225-00051 and TP-ENT-0424-00012 on the G000 sheet. 2. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: 1. Corrected development package. 2. Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home . Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code . |
||
| 05/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |