Permit Number: TC-COM-0426-00489
Parcel: 13624228C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0426-00489
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2026 Commercial Building APPROVED
04/20/2026 Site Zoning APPROVED
04/16/2026 Commercial Plumbing NOT REQUIRED
04/14/2026 Site Engineering NOT REQUIRED
04/16/2026 Water - PDSD NOT REQUIRED
04/26/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/16/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00489 (6710 E GOLF LINKS RD TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide an electrical demo plan showing all fixtures, receptacles, outlets, etc. that are being removed or relocated.
2. Provide updated electrical plans showing the electrical is compliant with the new occupancy classification, IEBC chapter 10.
04/16/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0426-00489
ADDRESS/PARCEL: 6710 E GOLF LINKS RD TUCSON, AZ 85730

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please show the existing mechanical system configuration, demonstrating that the space is conditioned and meets minimum ventilation requirements. Reference: Section 107.2.1, IBC 2024 and 403.1. IMC 2024.
04/23/2026 Fire New Construction REVIEW COMPLETED
04/09/2026 PDSD Application Completeness Express REVIEW COMPLETED