Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-0426-00484
Parcel: 14118602A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0426-00484
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2026 Commercial Electrical Standard APPROVED
04/14/2026 Site Engineering Standard APPROVED
04/30/2026 Site Zoning Standard APPROVED Ref: TD-DEV-0725-00181
04/28/2026 Water - PDSD Standard APPROVED
04/20/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
04/30/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/30/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please update the 2018 Code reference to the 2024 IBC on the structural sheets. IBC 107.2.1 Additionally, if special inspections are required for Post-Installed Anchors provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
2. Please provide the signed and sealed structural calculations, prepared by an Arizona licensed registrant, used in the design of this project. IBC 107.2.7 Roof structural for RTU’s
3. Please revise the sheet index to ensure it includes all sheets in the plan set and that the titles and numbering match the corresponding sheet labels. Provide a complete and consistent index for the entire set. Per IBC Section 107.2.1.
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/28/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2024.
2. Clarify the termination point for the 1-1/2” condensate drain for RHP-1 and RHP-2. Reference: Section 107.2.1, IBC 2024, and Section 307.2.1, IMC 2024, as amended by the City of Tucson.
3. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2024.
4. Show how the building pressurization is to be accommodated. Reference: Section 403.1, IMC 2024.
5. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Footnote g, Table 403.3.1.1, IMC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
04/28/2026 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 604.4, IPC 2024 and Section 606.4, ICC/ANSI A117.1-17.
2. Provide tempered water for the restroom lavatory with a device conforming to ASSE 1070. Coordinate the Plumbing Schedule description with Plumbing Note #8/P1.0. Reference: Section 419.5, IPC 2024.
3. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5.1, IECC 2018.
4. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping. Provide insulation per Table C403.11.3, IECC 2018 on the first 8 feet of supply and discharge piping. Reference: Section C404.4, IECC 2018.
5. Clarify the location of the water heater. Water heater schedule: “above FMS-1” (undefined). Water Heater Detail: “Set mounting height as high as possible.” Plumbing Note #7/P1.0: shelf 7’ AFF. Reference: Section 107.2.1, IBC 2024.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov