Permit Number: TC-COM-0426-00475
Parcel: 13205015H

Address:
3430 E 36TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0426-00475
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2026 Site Zoning Standard APPROVED
04/20/2026 Water - PDSD Standard APPROVED
04/21/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
04/09/2026 Site Engineering Standard NOT REQUIRED
06/11/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/11/2026 Commercial Building Standard REQUIRES RESUBMIT April 23, 2026
1st Review

Dean Alan Architects
Attn: Aaron Knepper
5151 E. Broadway Blvd. #1050
Tucson, Arizona 85711

Re: ARTO TILE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0426-00475
Stantec Project Number: 185215066
Stantec File Number: TUC-26-024

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M II-A 17,824 86 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Field welding.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Note on the cover of the drawings that special inspection is required for field welding. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. The code analysis does not clearly indicate compliance for allowable area of the building. Please determine if the building complies as a nonseparated occupancy (most restrictive requirements of the occupancies apply throughout) or separated occupancy and provide area calculations showing compliance. It does appear this building qualifies as a Group M nonseparated occupancy with frontage increase. [Ref. IBC 2024 Sec. 508]

Sheet A4.1

1. Please indicate that the point-of-use water dispenser will have a permanently mounted disposable cup dispenser installed adjacent to the cooler with the dispensing end between 34” and 48” above finished floor. [Ref. City of Tucson Policy 2008-21]

STRUCTURAL COMMENTS

General

1. Please provide structural calculations for this project.

Sheet

1. The Design Criteria indicates Seismic Design Category B for this project. The 2024 International Building Code designates the City of Tucson as a Seismic Design Category C. Please revise accordingly. [Ref. IBC 2024 Sec. 1613.2(1)]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/11/2026 Commercial Electrical Standard REQUIRES RESUBMIT April 23, 2026
1st Review

Dean Alan Architects
Attn: Aaron Knepper
5151 E. Broadway Blvd. #1050
Tucson, Arizona 85711

Re: ARTO TILE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0426-00475
Stantec Project Number: 185215066
Stantec File Number: TUC-26-024

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M II-A 17,824 86 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Field welding.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Note on the cover of the drawings that special inspection is required for field welding. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. The code analysis does not clearly indicate compliance for allowable area of the building. Please determine if the building complies as a nonseparated occupancy (most restrictive requirements of the occupancies apply throughout) or separated occupancy and provide area calculations showing compliance. It does appear this building qualifies as a Group M nonseparated occupancy with frontage increase. [Ref. IBC 2024 Sec. 508]

Sheet A4.1

1. Please indicate that the point-of-use water dispenser will have a permanently mounted disposable cup dispenser installed adjacent to the cooler with the dispensing end between 34” and 48” above finished floor. [Ref. City of Tucson Policy 2008-21]

STRUCTURAL COMMENTS

General

1. Please provide structural calculations for this project.

Sheet

1. The Design Criteria indicates Seismic Design Category B for this project. The 2024 International Building Code designates the City of Tucson as a Seismic Design Category C. Please revise accordingly. [Ref. IBC 2024 Sec. 1613.2(1)]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/11/2026 Commercial Mechanical Standard REQUIRES RESUBMIT April 23, 2026
1st Review

Dean Alan Architects
Attn: Aaron Knepper
5151 E. Broadway Blvd. #1050
Tucson, Arizona 85711

Re: ARTO TILE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0426-00475
Stantec Project Number: 185215066
Stantec File Number: TUC-26-024

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M II-A 17,824 86 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Field welding.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Note on the cover of the drawings that special inspection is required for field welding. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. The code analysis does not clearly indicate compliance for allowable area of the building. Please determine if the building complies as a nonseparated occupancy (most restrictive requirements of the occupancies apply throughout) or separated occupancy and provide area calculations showing compliance. It does appear this building qualifies as a Group M nonseparated occupancy with frontage increase. [Ref. IBC 2024 Sec. 508]

Sheet A4.1

1. Please indicate that the point-of-use water dispenser will have a permanently mounted disposable cup dispenser installed adjacent to the cooler with the dispensing end between 34” and 48” above finished floor. [Ref. City of Tucson Policy 2008-21]

STRUCTURAL COMMENTS

General

1. Please provide structural calculations for this project.

Sheet

1. The Design Criteria indicates Seismic Design Category B for this project. The 2024 International Building Code designates the City of Tucson as a Seismic Design Category C. Please revise accordingly. [Ref. IBC 2024 Sec. 1613.2(1)]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
06/11/2026 Commercial Plumbing Standard REQUIRES RESUBMIT April 23, 2026
1st Review

Dean Alan Architects
Attn: Aaron Knepper
5151 E. Broadway Blvd. #1050
Tucson, Arizona 85711

Re: ARTO TILE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0426-00475
Stantec Project Number: 185215066
Stantec File Number: TUC-26-024

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M II-A 17,824 86 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: None.
Special Inspections: Field welding.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the automatic fire sprinkler system [2018 IBC Sec. 903] and fire alarm system [2018 IBC Sec. 907] are to be provided as part of this project and are to be submitted as a separate permit (not a deferred submittal).

2. Note on the cover of the drawings that special inspection is required for field welding. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.

Sheet T1.0

1. The code analysis does not clearly indicate compliance for allowable area of the building. Please determine if the building complies as a nonseparated occupancy (most restrictive requirements of the occupancies apply throughout) or separated occupancy and provide area calculations showing compliance. It does appear this building qualifies as a Group M nonseparated occupancy with frontage increase. [Ref. IBC 2024 Sec. 508]

Sheet A4.1

1. Please indicate that the point-of-use water dispenser will have a permanently mounted disposable cup dispenser installed adjacent to the cooler with the dispensing end between 34” and 48” above finished floor. [Ref. City of Tucson Policy 2008-21]

STRUCTURAL COMMENTS

General

1. Please provide structural calculations for this project.

Sheet

1. The Design Criteria indicates Seismic Design Category B for this project. The 2024 International Building Code designates the City of Tucson as a Seismic Design Category C. Please revise accordingly. [Ref. IBC 2024 Sec. 1613.2(1)]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
04/29/2026 Fire New Construction Standard REVIEW COMPLETED
04/08/2026 PDSD Application Completeness Express REVIEW COMPLETED