Permit Number: TC-COM-0426-00459
Parcel: 141113750

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0426-00459
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2026 Commercial Electrical Standard APPROVED
04/20/2026 Commercial Plumbing Standard NOT REQUIRED
04/20/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
04/09/2026 Site Engineering Standard NOT REQUIRED
04/29/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/29/2026 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
Please contact me if you have any questions about the below comments. I can be reached at email mark.masek@tucsonaz.gov
1. Please amend the plans to clearly identify the specific use designation within the proposed Group F-1 occupancy, in accordance with IBC Section 302.2. The current submittal lists the occupancy classification but does not describe the actual use of the space.
Provide a brief description of the primary function (e.g., fabrication, manufacturing, assembly of products, processing operations, etc.) so that the occupancy classification can be properly verified.
2. Please provide a Hazardous Materials Inventory Statement (HMIS) for this project. The HMIS shall be prepared and submitted in accordance with International Building Code (IBC) Section 414.1.5 and International Fire Code (IFC) Section 5001.5, and shall include the following:
A complete inventory of all hazardous materials stored, used, or handled on site
Quantities (in pounds, gallons, or cubic feet, as applicable)
Physical state (solid, liquid, gas)
Hazard classification (per IFC)
Maximum allowable quantities (MAQs) and control area analysis
Storage and use locations, including identification on the floor plan
Safety Data Sheets (SDS) for each hazardous material
Please clearly demonstrate compliance with applicable MAQs per control area and identify any required hazardous occupancy classification(s) or fire protection features triggered by the quantities provided.
Failure to provide a complete HMIS may delay further review of this submittal.
3. Please provide sheet A3.0 and the elevation drawing as referenced on sheet A1.0 IBC 107.2.1
Please contact me if you have any questions about the above comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
04/20/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. Demonstrate energy code compliance for the building envelope using calculations based on the 2018 International Energy Conservation Code. Reference: Section C502.1, International Energy Conservation Code 2018.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
04/28/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-0426-00459
8181 S. Camino De Café Tucson, AZ 85747
Teledyne TI (1st Review)

TRANSMITTAL DATE: 4/28/2026

The site is zoned I-1 (UDC 4.7.29).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Please clarify the use. On the associated DP (TD-DEV-0423-00208) and past building permit for this site (TC-COM-1023-02502), the use was classified as craftwork. On this permit, sheet 1 says the use has changed and is now manufacturing but the title refers to “storage”.
2. Comment: Sheet 1 refers to the zoning as I-2, however this property is zoned I-1. Please update Sheet 1 with the correct zoning information.
3. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
04/20/2026 Water - PDSD Standard REQUIRES RESUBMIT Clarify the size of the proposed water meter and backflow preventer. The development plan, TD-DEV-0423-00208, shows a 1” meter with a 1” RP backflow, while the shell building plan, TC-COM-1023-02502, shows a 5/8” water meter and no mention of a backflow preventer.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov.
04/29/2026 Fire New Construction Standard REVIEW COMPLETED
04/08/2026 PDSD Application Completeness Express REVIEW COMPLETED