Permit Number: TC-COM-0426-00452
Parcel: 10702017A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0426-00452
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/03/2026 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0426-00452 (3143 N FREEWAY INDUSTRIAL LP TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. No permit history could be found for the ‘existing canopy’. Please provide permit number or other documentation to show that the canopy is permitted.
2. Provide the specification sheets for the new lighting fixtures being added. Show photometric data or other ratings that show these fixtures to be fully-shielded per the definition in the Outdoor Lighting Code, chapter 2.
3. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
4. Show lighting fixtures as fully shielded or a complete outdoor lighting calculation will be required.
04/03/2026 PDSD Application Completeness Express REVIEW COMPLETED