Permit Number: TC-COM-0425-00867
Parcel: 123031020

Address:
2504 E LEE ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0425-00867
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2025 Site Engineering NOT REQUIRED
05/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/16/2025 Commercial Building REQUIRES RESUBMIT May 7, 2025
1st Review

Dham Developers, LLC.
Attn: Clelia Dajlala
742 W. Grant Road Unit 207
Tucson, Arizona 85705

Re: PET GROOMING STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00867
Stantec Project Number: 185215066
Stantec File Number: TUC-25-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,017 21 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.


Sheet G1

1. Please revise the occupant load factor of 100 to 150. The occupant load factor for business occupancies is 150. [Ref. IBC 2018 Sec. 1004.5]

2. The ‘General Building Summary’ on this sheet indicates the Occupancy Group as a Group C. The IBC does not include a Group C occupancy. Please revise this to a Group B occupancy to correlate with the occupancy group indicated with Note 3 on this sheet. [Ref. IBC 2018 Sec. 304.1]

3. The occupant load of 37 indicated on the plumbing calculations conflicts the occupant load indicated with Note 3A on this sheet. Please revise this to correlate with the occupant load and revise the code edition indicated on the plumbing calculations to the 2018 IBC.

STRUCTURAL COMMENTS

General

1. Please provide an engineer’s structural analysis of the existing roof with the proposed 705lb roof top units indicating what structural modifications are required to support the new units, if any. [Ref. IEBC 2018 Sec. 303.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/16/2025 Commercial Electrical REQUIRES RESUBMIT May 7, 2025
1st Review

Dham Developers, LLC.
Attn: Clelia Dajlala
742 W. Grant Road Unit 207
Tucson, Arizona 85705

Re: PET GROOMING STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00867
Stantec Project Number: 185215066
Stantec File Number: TUC-25-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,017 21 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.


Sheet G1

1. Please revise the occupant load factor of 100 to 150. The occupant load factor for business occupancies is 150. [Ref. IBC 2018 Sec. 1004.5]

2. The ‘General Building Summary’ on this sheet indicates the Occupancy Group as a Group C. The IBC does not include a Group C occupancy. Please revise this to a Group B occupancy to correlate with the occupancy group indicated with Note 3 on this sheet. [Ref. IBC 2018 Sec. 304.1]

3. The occupant load of 37 indicated on the plumbing calculations conflicts the occupant load indicated with Note 3A on this sheet. Please revise this to correlate with the occupant load and revise the code edition indicated on the plumbing calculations to the 2018 IBC.

STRUCTURAL COMMENTS

General

1. Please provide an engineer’s structural analysis of the existing roof with the proposed 705lb roof top units indicating what structural modifications are required to support the new units, if any. [Ref. IEBC 2018 Sec. 303.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/16/2025 Commercial Mechanical REQUIRES RESUBMIT May 7, 2025
1st Review

Dham Developers, LLC.
Attn: Clelia Dajlala
742 W. Grant Road Unit 207
Tucson, Arizona 85705

Re: PET GROOMING STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00867
Stantec Project Number: 185215066
Stantec File Number: TUC-25-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,017 21 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.


Sheet G1

1. Please revise the occupant load factor of 100 to 150. The occupant load factor for business occupancies is 150. [Ref. IBC 2018 Sec. 1004.5]

2. The ‘General Building Summary’ on this sheet indicates the Occupancy Group as a Group C. The IBC does not include a Group C occupancy. Please revise this to a Group B occupancy to correlate with the occupancy group indicated with Note 3 on this sheet. [Ref. IBC 2018 Sec. 304.1]

3. The occupant load of 37 indicated on the plumbing calculations conflicts the occupant load indicated with Note 3A on this sheet. Please revise this to correlate with the occupant load and revise the code edition indicated on the plumbing calculations to the 2018 IBC.

STRUCTURAL COMMENTS

General

1. Please provide an engineer’s structural analysis of the existing roof with the proposed 705lb roof top units indicating what structural modifications are required to support the new units, if any. [Ref. IEBC 2018 Sec. 303.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/16/2025 Commercial Plumbing REQUIRES RESUBMIT May 7, 2025
1st Review

Dham Developers, LLC.
Attn: Clelia Dajlala
742 W. Grant Road Unit 207
Tucson, Arizona 85705

Re: PET GROOMING STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00867
Stantec Project Number: 185215066
Stantec File Number: TUC-25-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,017 21 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Note on the cover of the drawings that special inspection is required for epoxy and expansion anchors. Also, provide City of Tucson special inspection certificate(s) with Parts A and B completed. Make sure that the owner or their legal representative signs the form.


Sheet G1

1. Please revise the occupant load factor of 100 to 150. The occupant load factor for business occupancies is 150. [Ref. IBC 2018 Sec. 1004.5]

2. The ‘General Building Summary’ on this sheet indicates the Occupancy Group as a Group C. The IBC does not include a Group C occupancy. Please revise this to a Group B occupancy to correlate with the occupancy group indicated with Note 3 on this sheet. [Ref. IBC 2018 Sec. 304.1]

3. The occupant load of 37 indicated on the plumbing calculations conflicts the occupant load indicated with Note 3A on this sheet. Please revise this to correlate with the occupant load and revise the code edition indicated on the plumbing calculations to the 2018 IBC.

STRUCTURAL COMMENTS

General

1. Please provide an engineer’s structural analysis of the existing roof with the proposed 705lb roof top units indicating what structural modifications are required to support the new units, if any. [Ref. IEBC 2018 Sec. 303.1]

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
05/08/2025 Outdoor Lighting REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0425-00867
ADDRESS/PARCEL: (2504 E LEE ST TUCSON, AZ 85716)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter.
COMMENTS:
1. Please provide the spec sheets for all full cutoff light fixtures. Please provide photometric data as well (OLC 104.2)
a. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
2. Please resubmit
05/21/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0425-00867
2504 E LEE ST. - C-1
TI Animal Services (1st Review)

TRANSMITTAL DATE: ‎May 21, 2025

Resubmit revised drawings with a detailed response letter stating how all Zoning Review Section comments were addressed.

This site is located in the C-1 zone (UDC 4.7.20). Animal Services is a permitted use in the zone (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.D.1, .2, .3, & .4 and 4.9.13.O or 4.9.4.D.7 & 4.9.4.D.10-.15.

1. Clearly demonstrate that Use Specific Standards 4.9.4.D.1, .2, .3, & .4 and 4.9.13.O or 4.9.4.D.7 & 4.9.4.D.10-.15 are met.

2. Provide documentation that this site was an approved commercial use, i.e. approved site plan or C of O as it appears that the prior use was multifamily. A development package meeting the requirements of AM 2-06 maybe required.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/13/2025 Fire New Construction REVIEW COMPLETED Fire extinguishers shall comply with section 906 of the 2018 IFC
05/02/2025 PDSD Application Completeness Express REVIEW COMPLETED
05/16/2025 Water - PDSD REVIEW COMPLETED