Permit Number: TC-COM-0425-00867
Parcel: 123031020

Address:
2504 E LEE ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-0425-00867
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2025 Site Zoning APPROVED
08/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/20/2025 Commercial Building REQUIRES RESUBMIT August 20, 2025
3rd Review

Dham Developers, LLC.
Attn: Clelia Dajlala
742 W. Grant Road Unit 207
Tucson, Arizona 85705

Re: PET GROOMING STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00867
Stantec Project Number: 185215066
Stantec File Number: TUC-25-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,017 21 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. New Comment: The latest submittal is missing the structural calculations for the masonry wall in-fill and lintel designs. Please ensure this is reuploaded in the next submittal.

Sheet G1

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

General

1. Addressed.

2. New Comment: The design of the reinforcement needed for the mechanical units included in the structural calculations provided with this submittal must be incorporated into the plan-set and not just included within the calculations. Please incorporate the new structural reinforcement design into the construction drawings.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/20/2025 Commercial Electrical REQUIRES RESUBMIT August 20, 2025
3rd Review

Dham Developers, LLC.
Attn: Clelia Dajlala
742 W. Grant Road Unit 207
Tucson, Arizona 85705

Re: PET GROOMING STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00867
Stantec Project Number: 185215066
Stantec File Number: TUC-25-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,017 21 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. New Comment: The latest submittal is missing the structural calculations for the masonry wall in-fill and lintel designs. Please ensure this is reuploaded in the next submittal.

Sheet G1

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

General

1. Addressed.

2. New Comment: The design of the reinforcement needed for the mechanical units included in the structural calculations provided with this submittal must be incorporated into the plan-set and not just included within the calculations. Please incorporate the new structural reinforcement design into the construction drawings.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/20/2025 Commercial Mechanical REQUIRES RESUBMIT August 20, 2025
3rd Review

Dham Developers, LLC.
Attn: Clelia Dajlala
742 W. Grant Road Unit 207
Tucson, Arizona 85705

Re: PET GROOMING STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00867
Stantec Project Number: 185215066
Stantec File Number: TUC-25-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,017 21 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. New Comment: The latest submittal is missing the structural calculations for the masonry wall in-fill and lintel designs. Please ensure this is reuploaded in the next submittal.

Sheet G1

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

General

1. Addressed.

2. New Comment: The design of the reinforcement needed for the mechanical units included in the structural calculations provided with this submittal must be incorporated into the plan-set and not just included within the calculations. Please incorporate the new structural reinforcement design into the construction drawings.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
08/20/2025 Commercial Plumbing REQUIRES RESUBMIT August 20, 2025
3rd Review

Dham Developers, LLC.
Attn: Clelia Dajlala
742 W. Grant Road Unit 207
Tucson, Arizona 85705

Re: PET GROOMING STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-0425-00867
Stantec Project Number: 185215066
Stantec File Number: TUC-25-050

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B V-B 2,017 21 No No
Separate Permits: None.
Deferred Submittals: None.
Special Inspections: Epoxy and expansion anchors.

ARCHITECTURAL COMMENTS

General

1. Addressed.

2. New Comment: The latest submittal is missing the structural calculations for the masonry wall in-fill and lintel designs. Please ensure this is reuploaded in the next submittal.

Sheet G1

1. Addressed.

2. Addressed.

3. Addressed.

STRUCTURAL COMMENTS

General

1. Addressed.

2. New Comment: The design of the reinforcement needed for the mechanical units included in the structural calculations provided with this submittal must be incorporated into the plan-set and not just included within the calculations. Please incorporate the new structural reinforcement design into the construction drawings.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com