Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-0425-00852
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2025 | Commercial Electrical | APPROVED | |||
| 05/20/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/19/2025 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. Please provide a sealed evaluation prepared by an Arizona licensed engineer verifying the existing roof structure will be able to resist the additional load of the new kitchen hood. INC 107.2.7 2. Please provide design, calculations and provide drawing details prepared by an Arizona licensed engineer, to show the attachment of the new units to the existing roof structure. IBC 107.2.1 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 05/20/2025 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Show the location of the required control panel and utility cabinet for the Type I hood. Reference: Section 304.1, IMC 2018. 2. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2018. 3. Provide a roof plan to show the location of the exhaust fan for the proposed Type I hood as it relates to the existing mechanical equipment on the roof and building openings. Reference: Section 501.3.1, IMC 2018. 4. Verify that adequate general room exhaust is provided for cooking appliance that are not required to be located under a Type II hood. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018. 5. Show that the heat and moisture loads from the proposed cooking appliances that are not located under a Type II hood are included in the HVAC load calculations for the space. Reference: Section 507.3, IMC 2018. 6. Verify that the hood canopy extends at least 6” horizontally on all open sides beyond the edge of the top horizontal surface of the appliances under the hood. Reference: Section 507.4.1, IMC 2018. 7. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.2.4, IMC 2018 (the hood hanging weight plus the weight of personnel working in or on the hood). Verify that the installation of the hood , in addition to the existing roof-mounted equipment, does not exceed the structural capability of the roof. Reference: Section 302.1, IMC 2018. 8. Provide adequate make up air for the kitchen exhaust hood. Reference: Section 508.1 IMC 2018 |
||
| 05/20/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Verify that the new drink dispenser will not require the installation of an indirect waste receptor. Reference: Section 107.2.1, IBC 2018. 2. Verify that the existing grease interceptor will be adequate for the new use. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson. 3. The relocated hand sink will not be connected to the grease waste system. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson. |
||
| 05/19/2025 | Fire New Construction | REVIEW COMPLETED | |||
| 05/05/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |