Permit Number: TC-COM-0425-00852
Parcel: 12517032A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.4

Permit Number - TC-COM-0425-00852
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/08/2025 Commercial Mechanical REQUIRES RESUBMIT 1. The supply airflow rate of the rooftop units does not play a part in the air balance of the building. You need to increase the amount of outside air to achieve balance. [Second comment: The equipment schedule only identifies 190 CFM of outside air being supplied to the kitchen; approximately 510 CFM of additional outside air is required. Increasing the total supply airflow for each rooftop unit does not introduce any additional outside air. Provide an air balance schedule for the kitchen per Section 508.1.2, IMC 2018. [Initial comment: Provide adequate make up air for the kitchen exhaust hood. Reference: Section 508.1 IMC 2018.]
2. The roof plan has been revised and the outside air intake for RTU-2 is now located within ten feet of the new exhaust fan. Reference: Section 506.3.13.3.3, IMC 2018.
07/08/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Comment not addressed. [Second comment: Comment not addressed. [Initial comment: Verify that the new drink dispenser will not require the installation of an indirect waste receptor. Reference: Section 107.2.1, IBC 2018.]
2. Comment not addressed. [Second comment: Comment not addressed. [Initial comment: Verify that the existing grease interceptor will be adequate for the new use. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.]
3. Comment not addressed. [Second comment: Comment not addressed. [Initial comment: The relocated hand sink will not be connected to the grease waste system. Hand sinks in the kitchen are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, “HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED.” Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.]
07/03/2025 PDSD Application Completeness Express REVIEW COMPLETED