Permit Number: TC-COM-0425-00850
Parcel: 12507172A

Address:
2513 E 6TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0425-00850
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2025 Site Zoning Standard APPROVED
05/22/2025 Water - PDSD Standard APPROVED
05/23/2025 Outdoor Lighting Standard NOT REQUIRED
05/29/2025 Site Engineering Standard NOT REQUIRED
05/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2025 Commercial Building Standard REQUIRES RESUBMIT 1. Sheet A0.0 Provide Occupancy Load Sign-age in the A3 area. IBC 1009.9 Provide Sign-age at egress doors per 1010.1.9.4.
2. Sheet A1.0 Provide Accessible seating at Bar locations and other seating areas as required by IBC Chapter 11.
3. Sheet A1.0 Will there be any seating in covered patio areas? if there is show occupancy numbers.
4. Sheet A1.0 Show enlarged plan for restrooms, to verify they comply with ICC A117.
05/14/2025 Commercial Electrical Standard REQUIRES RESUBMIT 1. Sheet E2.0 Show location of all exit signs and emergency lighting per NEC 700.12 (F)(2).
2. Sheet E4.0 Provide GFCI service outlets within 25' of equipment on roof.
05/14/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Sheet M1.0 Provide a Air Balance report prior to final inspection. Per IMC.
2. Sheet M1.0 Provide smoke detectors in returns over 2000CFM, and supply ducts over 15000CFM. IMC
05/14/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Sheet P0.0 Plumbing sheets shall be sealed by an Arizona Registrant.
2. Sheet P3.0 Provide slab repair detail for any all plumbing trenches.
05/15/2025 Fire New Construction Standard REVIEW COMPLETED Fire alarm and fire sprinklers upgrades will require a separate submittal and permit. kitchen hood fire suppression will also require a separate submittal and permit.
05/02/2025 PDSD Application Completeness Express REVIEW COMPLETED