Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0425-00845
Parcel: 11516022A

Address:
2200 N FREEWAY

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-0425-00845
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/12/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/12/2025 Signs REQUIRES RESUBMIT June 8. 2025
2200 N Freeway - TC-COM-0425-00845; COT 535
RESUBMITTAL - Replace Electrical Meter and Disconnect
Comments:
1. The electrical engineer states that information about the existing meter
socket is not available, and that because the City of Tucson has allowed the
proposed replacement at other locations, the use of the proposed meter
socket should be allowed. I make the following comment:
This is an issue because I am responsible to review the application to
ensure that any item that is to be replaced is indeed replaced "like for like."
Although the City of Tucson may have allowed the proposed meter socket
previously, according to the Settlement Agreement, the proposed socket
cannot be more vigorous (longer life span) or has heftier specifications than
the one being replaced, unless the item is no longer available. Square D
makes a 100 amp meter socket.
Perhaps Clear Channel has the specifications for the existing meter socket,
or they can send out personnel who have access to the location to collect
that information. The electrical service is on railroad property and is fenced
off. I visited the location to observe the installation myself, in an attempt to
expedite the review process, but I couldn't get passed the fence. It is the
applicant's responsibility to provide the required information.
2. Engineer's clarification of BRC's comment #2 is appreciated.
Kathi McLaughlin, BRC Reviewer
06/12/2025 Site Zoning REQUIRES RESUBMIT Refer to Sign comments.
06/02/2025 PDSD Application Completeness Express REVIEW COMPLETED