Permit Number: TC-COM-0425-00841
Parcel: 12513002D

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.5

Permit Number - TC-COM-0425-00841
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/30/2025 Commercial Mechanical Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0425-00841
ADDRESS/PARCEL: (3200 E SPEEDWAY BL TUCSON, AZ 85716
The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS
1. The requested heating and cooling load calculations have not been submitted. These are the engineering calculations that show how much heating and cooling the building requires based on its square footage, insulation levels, windows, orientation, etc.
Reference: C403.1.1 Calculation of heating and cooling loads. (2018 IECC)
• Design loads associated with heating, ventilating and air conditioning of the building shall be determined in accordance with ANSI/ASHRAE/ACCA Standard 183 or by an approved equivalent computational procedure using the design parameters specified in Chapter 3. Heating and cooling loads shall be adjusted to account for load reductions that are achieved where energy recovery systems are utilized in the HVAC system in accordance with the ASHRAE HVAC Systems and Equipment Handbook by an approved equivalent computational procedure