Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-0425-00841
Parcel: 12513002D

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4

Permit Number - TC-COM-0425-00841
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/02/2025 Commercial Mechanical Express REQUIRES RESUBMIT The submitted COMcheck Mechanical Compliance Certificate verifies that the proposed replacement HVAC units comply with the energy efficiency requirements of the 2018 IECC. The requested heating/cooling load calculations to justify the capacities of the proposed units has not been submitted. See Section C403.1.1, IECC 2018 for the heating/cooling load calculation requirements. [Initial comment: Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018).]
08/28/2025 PDSD Application Completeness Express REVIEW COMPLETED