Permit Number: TC-COM-0425-00841
Parcel: 12513002D

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-0425-00841
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/22/2025 Commercial Mechanical Express REQUIRES RESUBMIT 1. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018).
2. A test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.
07/18/2025 PDSD Application Completeness Express REVIEW COMPLETED