Permit Number: TC-COM-0425-00837
Parcel: 11006021A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-0425-00837
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/28/2025 Commercial Electrical Express REQUIRES RESUBMIT Commercial Electrical Review TC-COM-0425-00837 (3114 N ALVERNON WY TUCSON, AZ 85712)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide an electrical plan showing any/all electrical work.
Plans shall include, but may not be limited to items below:
3. Provide new and updated panel schedules, showing the circuits that are being modified, added or removed. NEC arts;300 and 408.4.
4. Designate the circuit number, that corresponds to the panel schedule, at the location of each new, modified or repaired light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4.
5. Show all wiring methods in detail for all new branch circuit wiring and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
6. Provide electrical load calculations, for the Main Service Panel and Sub-panels, Per NEC 220.40.
7. Show grounding and bonding of equipment per NEC 250.

Additional comments may be forthcoming based on a complete plan-set.