Permit Number: TC-COM-0425-00836
Parcel: 10821018Y

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.4

Permit Number - TC-COM-0425-00836
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2026 Site Zoning APPROVED
06/01/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/27/2026 Commercial Mechanical REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0425-00836
ADDRESS/PARCEL: 4205 N CAMPBELL AV TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Previous comment not fully addressed. Please clarify the discrepancy between the 750 CFM exhaust noted in the exhaust fan schedule and the 400 CFM shown on the mechanical floor plan.. (Previous comment - The Exhaust Fan Schedule calls for an exhaust flow rate of 875 CFM but only 400 CFM of exhaust is identified on the mechanical floor plan.) Reference: Section 107.2.1, IBC 2018
05/27/2026 Commercial Plumbing REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0425-00836
ADDRESS/PARCEL: 4205 N CAMPBELL AV TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Note 3 of the Fixture and Piping Connection Schedule calls out for an 80-gallon electric water heater, but a tankless water heater is shown on the Water Plan. Please correct. Reference: Section 107.2.1, IBC 2018
05/27/2026 Water - PDSD REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0425-00836
ADDRESS/PARCEL: 4205 N CAMPBELL AV TUCSON, AZ 85719

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov.

COMMENTS:

1. Previous comment not addressed. This meter appears to be serving more than just this one suite. And it appears to be a 1.5” water meter instead of a 1-1/4” meter as stated on the water plan. Please verify. (Previous comment - Provide the size of the water meter serving this suite and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.)
2. Previous comment not addressed. (Previous comment - Please include the pressure drop of the assembly in the Domestic Water Calculation. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code)
06/01/2026 Fire New Construction REVIEW COMPLETED
05/15/2026 PDSD Application Completeness Express REVIEW COMPLETED