Permit Number: TC-COM-0425-00833
Parcel: 141366950

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-0425-00833
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/16/2025 10:48:36 AM

Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 5/14/2025 4:22:50 PM
05/19/2025 Commercial Mechanical Standard APPROVED Mechanical(M) Reviewer
John Graves
jgraves@mtcinspectors.com
Approved
Reason:
Date Completed : 5/2/2025 3:50:37 PM
05/21/2025 Water - PDSD Standard APPROVED
05/29/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/19/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 5/12/2025 7:14:34 PM
E1.2 EXTERIOR SITE PHOTOMETRIC PLAN: Exterior lighting Lumen calculation exceeds local lumens per acre code
allowance. Will need to redesign or revise lighting fixture selections to meet local lighting code of Tucson and Pima County’s
2023 Outdoor Lighting Code.
05/19/2025 Commercial Plumbing Standard REQUIRES RESUBMIT Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 5/18/2025 8:50:22 PM
First Plumbing Review:
1). Plan Page P1.3: The individual water connected pieces of beverage equipment/dispensers/appliances need individual
backflow devices. Add backflow devices to the individual water connected pieces of beverage
equipment/dispensers/appliances. -2018 IPC 608.1. & 608.17
2). Plan Page P1.1 & A8.3: Missing adjacent overflow scupper sizing info , illustration & detail. Add adjacent overflow
scupper sizing info , illustration & detail. -2018 IPC 1106.5, 1108
3). Plan Page A3.3: Missing dual lavatory side wall & fixture to fixture separation distances. Add dual lavatory side wall &
fixture to fixture separation distances. -2018 IPC 405.3.1
05/08/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-0425-00833 (6930 E CAMINO BOLEADORAS TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. >> Remove the “For Information Only” notation on E1.2 and E1.3. These sheets shall be sealed by the appropriate EOR.
2. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan.
3. List the Lighting Area per OLC chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4.
4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
5. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).

6. This site requires an Outdoor Lighting Special Inspection per 106.2.1. Provide a Special Inspection Certificate with parts A and B completed and sealed. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/29/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-0425-00833
6930 E CAMINO BOLEADORAS

Site Engineering comments are as follows:
1. Although the site plans for TC-COM-0425-00833 and development package, TD-DEV-0225-00041, appear to match, this commercial building permit cannot be approved until the DP is approved by all reviewers. UDC Article 3.3.3.7.a
Ryan Insalaco – ryan.insalaco@tucsonaz.gov
05/23/2025 Site Zoning Standard REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-0425-00833 - TD-DEV-0225-00041
6930 E CAMINO BOLEADORAS. - PAD-7
General Merchandise Sales (1st Review)

TRANSMITTAL DATE: ‎May 23, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in PAD-7 (UDC 4.7.24). General Merchandise Sales use is a permitted use in the PAD.

1. Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-0225-00041and although it appears that the building plan is in compliance until the DP is approved by all review agencies Zoning cannot approve this plan.

2. Detail 14 sheet 3 does not match the short-term bicycle rack shown on the DP and does not meet minimum spacing requirements, UDC Article 7.4.9.B.2.d & f and Figure 7.4.9-C.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/19/2025 Fire New Construction Standard REVIEW COMPLETED The following permits are required:
1. Fuel tanks operational permit; contact Jesus.silva@tucsonsz.gov
2. CO2 operational permit
3. Propane fuel operational Permit.
04/30/2025 PDSD Application Completeness Express REVIEW COMPLETED