Permit Number: TC-COM-0425-00795
Parcel: 108240890

Address:
2474 E RIVER RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-0425-00795
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2025 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-0425-00795
ADDRESS/PARCEL: (2474 E RIVER RD TUCSON, AZ 85718)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval.

COMMENTS:
1. LOCATION IS NOT CLEAR
a. Please provide a site plan, locate and label the space being enclosed.
2. FLOOR PLAN
a. Submit a floor plan of the entire structure. Show all the doors and windows allowing the city to see how the means of egress may be affected.
3. 2018 IRC – Sheet 1 of 4, item 7
a. The 2018 International Residential Code is referred on this submission.
b. This is a commercial structure, please remove any IRC reference and use the International Building Code (IBC),
4. SPACE USE
a. Please inform the city as to what this room is going to be used for.
b. Enclosing a space will require ventilation and possibly heating.
c. Please tell us what you are going to do with those two existing doors and that short interior wall.
d. Should both door be kept, ensure that the required accessible space between doors are met per ICC A117.1 figure 404.2.5 drawing configuration b.
e. Will light be installed within the space.
5. WINDOW
a. Provide information as to the U value and Solar Heat Gain Coefficient of the window glass being proposed.
6. Please resubmit.
If you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976
05/08/2025 Site Engineering REQUIRES RESUBMIT Provide a site plan showing the location of this elevation A, and the patio area to be enclosed.
05/07/2025 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-0425-00795
2474 E RIVER RD– O-3
Office – Enclose back patio (1st Review)

TRANSMITTAL DATE: May 7, 2025

DUE DATE: May 7, 2025

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the O-3 zone (UDC 4.7.15). Admin Office is an allowed use in the Zone, (UDC Table 4.8-3). See Use-Specific Standard 4.9.13.K

1. The proposed enclosure of a patio is an expansion of gross floor area (GA) and requires a development package (DP), UDC Article 3.3.3.G.2.c. A Development Package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1 . The DP is a separate submittal from the building plans.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/05/2025 Fire New Construction REVIEW COMPLETED
04/23/2025 PDSD Application Completeness Express REVIEW COMPLETED