Permit Number: TC-COM-0425-00794
Parcel: 132110720

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0425-00794
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2025 Commercial Electrical Standard APPROVED
08/07/2025 Outdoor Lighting Standard APPROVED
08/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/14/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. The fixture drain from the automatic clothes washer in unit 2 appears to connect to a 2” horizontal branch. [Initial comment: The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Reference: Section 406.2, IPC 2018.]
2. The basis of your pipe sizing is an available water pressure of 65 PSI, but Tucson Water shows an available pressure range of only 37.27 to 44.27 PSI for your address. [Initial comment: For the use of PEX tubing, provide a branch tube sizing chart showing the correct size of PEX tubing to be used as a substitute for the copper pipe shown on the drawings. Reference: Sections 303.2 and 604.3, IPC 2018.]
07/23/2025 PDSD Application Completeness Express REVIEW COMPLETED