Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.5
Permit Number - TC-COM-0425-00787
Review Name: COMMERCIAL REVIEW - LIMITED v.5
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/31/2025 | Outdoor Lighting | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-0425-00787 (2950 N COLUMBUS BL TUCSON, AZ 85712) 3rd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Outdoor Lighting Review: >>> The following comments were not addressed. The specification sheets do not meet the requirements of the Outdoor Lighting Code requirements found in OLC 104.2. Nor do the specification sheets provide the total lumens calculations as required. The requirements must be part of the sealed plans provided by the Engineer of Record. 1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan 2. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 3. Show compliance with total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. 4. Show compliance with shielding requirements and light trespass per 401.3. 5. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded. 6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. 7. Specify any exceptions used. 8. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 07/23/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |