Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-0425-00755
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/07/2025 | Commercial Building Standard | APPROVED | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 5/1/2025 4:20:16 PM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Approved Reason: Date Completed : 5/1/2025 8:08:50 PM |
||
| 05/07/2025 | Commercial Electrical Standard | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved Reason: Date Completed : 5/3/2025 5:27:36 PM |
||
| 05/13/2025 | Site Zoning Standard | APPROVED | |||
| 05/13/2025 | Water - PDSD Standard | APPROVED | |||
| 05/01/2025 | Outdoor Lighting Standard | NOT REQUIRED | |||
| 05/13/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 05/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/07/2025 | Commercial Mechanical Standard | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 5/5/2025 1:13:45 PM 1. General - Provide RTU Schedule. Confirm Units Total CFM values to each unit specific Supply/Return grills/diffusers total CFM values. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. 2. General - Provide Exhaust fan schedule. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. 3. General - Provide Air Balance Schedule. - 2018 IMC Section 508.1.2 Air Balance. 4. General - Provide specifications for MAU. If unit air is not tempered provide Heat Load Calculation/Summary. Show all cooling/heating O/A loads on calculations. Confirm unit sizing design. - 2018 IMC Section 508.1.1 Makeup air temperature. - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads. |
||
| 05/07/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 5/6/2025 10:28:11 PM FIRST PLUMBING REVIEW: 1). Plan Page P1.0: missing total gas system length & sizing table used. Add total gas system length & sizing table used.- 2018 IFGC 402.3 2). Plan Page P1.0: Missing notation of what the furthest most remote gas line use is where it appears to be valved and capped? And gas system notation for the use of the valved capped gas line that exits the building. -2018 IFGC 106.3.1 3). Plan page X1.1: Missing fixture spacing measurements for dual lavatory sidewall & center to center spacing. Also missing adult toilet fixture spacing side wall to center measurements. Add fixture spacing measurements for all scenarios shown on floor plan. -2018 IPC 404.2, 405.3.1 |
||
| 05/07/2025 | Fire New Construction Standard | REVIEW COMPLETED | Fire alarm, fire sprinklers and kitchen hood fire suppression alterations will require a separate submittal and permit. | ||
| 04/22/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |