Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - TC-COM-0425-00755
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/23/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/23/2025 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-0425-00755 ADDRESS/PARCEL: (7080 E 22ND ST Unit:UNIT 104 TUCSON, AZ 85710) Submit your revised drawings along with a response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. Please submit a new air balance report showing MAU-1 meeting the required CFM. |
||
| 10/21/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 10/22/2025 | Water Sterilization Report (Deferred Submittal) Express | REVIEW COMPLETED |