Permit Number: TC-COM-0425-00755
Parcel: 13502134M

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-0425-00755
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/11/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 6/8/2025 10:27:34 AM
06/10/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/11/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 6/10/2025 9:31:20 AM
1. (RESOLVED) - General - Provide RTU Schedule. Confirm Units Total CFM values to each unit specific Supply/Return grills/diffusers total CFM values. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents.
2. (UNRESOLVED) - General - Provide Exhaust fan schedule. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents.
i. Exhaust total CFM shown on the Mechanical New Work Key Notes do not match what is on the Air Balance Schedule
3. (UNRESOLVED) -General - Provide Air Balance Schedule. - 2018 IMC Section 508.1.2 Air Balance. ◦ Design plans for a facility with a commercial kitchen ventilation system shall include a schedule or diagram
indicating the design of outdoor air balance. The design outdoor air balance shall indicate all exhaust and replacement air for the facility, plus the net exfiltration if applicable. The total replacement air airflow rate shall equal the total exhaust airflow rate plus the net exfiltration
i. Total Exhaust CFM on the Air Balance Schedule do not match what is shown on the Mechanical New Work Key Notes.
4. (UNRESOLVED) - General - Provide specifications for MAU. If unit air is not tempered provide Heat Load Calculation/Summary. Show all cooling/heating O/A loads on calculations. Confirm unit sizing design. - 2018 IMC
Section 508.1.1 Makeup air temperature. - 2018 IECC Section C403.1.1 Calculation of heating and cooling loads. i. No information provided for MAU systems. Provide CFM quantity on plans as a minimum to confirm Air Balance Schedule.
06/04/2025 PDSD Application Completeness Express REVIEW COMPLETED